DSL-150

Back to Enerstat Slimline Digital Thermostats

COOL ONLY, 3 WIRE CONTROLLER WITH SELECTABLE FAN

GENERAL DESCRIPTION

The DSL-150 controller is designed for new or replacement applications of "cooling only" systems. The DSL-150 represents the latest in solid-state surface mount electronics and manufacturing techniques incorporated into a extremely low profile, ultra-slim white ABS plastic case. The DSL-150 offers "user friendly" control of cooling equipment along with an easy-to-read vertical LCD that displays complete operations status. A direct-wire, easy to-install subbase mounts on a standard vertical outlet box or any dry wall surface using anchors and hardware provided.

STANDARD FEATURES
  • Selectable Celsius or Fahrenheit temperature display.
  • Fan selector for continuous fan operation.
  • Built-in short cycle protection.
  • Electronic circuitry replaces conventional mechanical anticipator.
  • Internal switch to lock-out the keypad to prevent unauthorised tampering.
  • 45 second fan purge after cooling call.
  • Day/Night button for user selectable alternate setpoint for manual setback.
  • Solid state electronic output.
  • Does not require a battery (always maintains the last setpoint and mode of operation following power outages of any duration.)
  • Lockable access cover.
  • Remote clock terminals.
  • Outdoor temperature sensor (optional).
  • Indoor Remote Temperature Sensor (optional).
  • Built-in anticipation & droop.
  • Minimum On/Off Times - (2 or 4 minutes selectable).

  • SPECIFICATIONS
    Rated Voltage 20-30 Vac, 24 nominal
    Rated Current 0.08 Amps to 1.5 Amps continuous per output with surges to 4 Amps Max.
    Control Range Cooling: 16 to 40 C in 1 C Steps
    Controller measurement range 0 to 48 C
    O.D.T. Measurement Range - 48 C to 48 C
    Control Accuracy ± 0.5 C At 20 C
    Dimensions: 114mm x 102mm x 22mm
    Termination: R, Y, G
    Minimum wires required 3

    OUTPUT TERMINAL FUNCTIONS

    RC 24 Vac supply from cooling equipment
    Y Cooling energised on a call for cooling
    G Fan energised
    CLK1 & CLK2 Use with remote clock/timer for alternate setpoints

    RS2 & RS1 & RS+V Use to connect Outdoor Temperature Sensor Option and/or Indoor Remote Sensor option. Refer to the instructions included with the sensors.
    - Equipment load resistors (provided) may may be required on the 'y' and 'G' switching circuit if the equipment loads do not draw a minimum of 0.08 amps.
    - Connect load resistors at the equipment.

    Back to Enerstat Slimline Digital Thermostats