DSL- 345

SINGLE SETPOINT HEATING / COOLING ONLY CONTROLLER WITH AUTO CHANGEOVER AND REVERSING VALVE OUTPUTS FOR HYDRONIC AND FAN COIL APPLICATIONS
- 1 HEATING / 1 COOL

GENERAL DESCRIPTION

The DSL- 345 single stage controller is designed for new or replacement commercial or residential applications, including some hydronic systems, ie. fan coils. The DSL-345 represents the latest in solid-state surface mount electronics and manufacturing techniques incorporated into a extremely low profile, ultra-slim white ABS plastic case. The DSL-345 offers "user friendly" control of heating/cooling equipment along with an easy-to-read vertical LCD that displays complete operations status. A direct-wire, easy to-install subbase mounts on a standard vertical outlet box or any dry wall surface using anchors and hardware provided.

STANDARD FEATURES
  • Single Setpoint.
  • Selectable Celsius or Fahrenheit temperature display.
  • Fan selector for continuous fan operation.
  • Built-in short cycle protection.
  • Electronic circuitry replaces conventional mechanical anticipator.
  • Internal switch to lock-out the keypad to prevent unauthorised tampering.
  • Does not require a battery (always maintains the last setpoint and mode of operation following power outages of any duration.)
  • Thermostat output using relays
  • Lockable access cover.
  • Indoor Remote Temperature Sensor (optional).
  • Independent circuit switching.
  • 1 C Heat/Cool separation.
  • Built-in anticipation & droop.
  • Minimum on/off times (2 or 4 minute selectable).

  • SPECIFICATIONS
    Rated Voltage 20-30 Vac, DC 24 Nominal
    Rated A.C Current: 0.050 Amps to 0.75 Amps continuous per output with surges to 3 Amps Max.
    Rated D.C. Current: 0.0 Amps to 0.75 Amps continuous per output with surges to 3 Amps Max.
    Control Range Cooling: 16 to 40 C in 1 C Steps
    Heating: 5 to 30 C in 1 C Steps
    Controller measurement range 0 to 48 C
    Control Accuracy ± 0.5 C At 20 C
    Minimum Deadband: (between heating and cooling) 1 °C
    Dimensions: 114mm x 102mm x 22mm
    Termination: R, X, W, Y, G, O, B
    Minimum wires required 7

    OUTPUT TERMINAL FUNCTIONS

    W1 Energises on a call for first stage heat
    Y1 Energises on a call for first stage cool
    G Energises the fan circuit on a call for heating or cooling
    R Independent Switching Voltage
    24 Vac 24 Vac
    24 Vac (C) 24 Vac (Common)
    O Energises the valve in the cooling mode
    B Energises the valve in the heating mode
    RS2 & RS1 & RS+V Use to connect the Indoor Remote Sensor Option. Refer to the instructions included with the sensors.

    Back to Enerstat Slimline Digital Thermostats